Indicator 4 outputs and RS485
– Panel mount indicator: 78 x 35 mm, depth 75.5 mm
– 1 Configurable probe input
– 2 digital inputs
– Up to 4 outputs
– Built-in independent timer
– Counter for worked days and hours
– TTL or RS485 Modbus-RTU ports
– 1 display line, 4 digit, h: 12 mm, red colour
Process inputs:
1 temperature probe input
– Thermocouples: J, K, R, S,T
– PTC KTY81-121 (990 Ω @ 25 °C)
– NTC 103AT-2 (10KΩ @ 25 °C)
– RTD: Pt100
– Voltage (V): 0..1 V, 0/1…5 V , 0/2…10 V
– Voltage (mV): 0…50 mV, 0…60 mV, 12 …60 mV
– Current (mA): 0/4…20 mA
– Custom linearisation and IR probes (J.K type)
Overall accuracy: ± (0,5 % span ± 1 digit @25 °C); Tc S: ± (1 % span ± 1 digit @ 25 °C)
2 digital inputs
– Free Voltage
Keyboard
Mechanical: 4 multifunction keys
Process outputs
Up to 4 Digital outputs
OUT1
– RELAY SPDT, 8A
– SSR Drive
OUT2
– RELAY SPDT, 8A
– SSR Drive
OUT3/OUT4
– RELAY SPST-NO, 5A
– SSR Drive
OUT5(Note1)
– SSR Drive 0…5Vdc, ±20%, 30 mA max
Power supply:
– 12 VAC/VDC
– 24VDC/VAC
– 100… 240 Vac (50/60 Hz)
Transmitter power supply: 10 V DC (±10%), 20 mA max.
Functions
– Indication
– Independent timer with 4 functioning modes
(optional)
– Counter for days and hours worked
with programmable threshold for programmed maintenance
Alarms
– Up to 3 configurable alarms + loop break alarm
Communication and programming:
Interfaces
Communication on TTL port to:
– Universal programming key
– Remote display
– RS 485 serial interface
RS 485 port with ModBus RTU protocol (optional)
Programming/configuration tools:
– Configurable parameter level “Promotion”
– Configuration software available for PC
Measured value : process, temperature, universal
Display : digital
Type : panel-mount
Other characteristics : programmable, RS-485, Modbus, remote, TTL
Applications : for Pt100 probe, transmitter
Reviews