Supply Voltage –
8…36 VDC
Input Types –
Thermocouple: B,E, J, K, L, N, R, S, T, U
Rezistans Thermometer: PT100
Input Empedance – Thermocouple: 10MΩ
Measurement Resolution – 16 bit
Sampling Frequency – 100ms
Analog Output – 4-20mA, 20-4mA
Analog Output Resolution – 16 bit
Transfer Error – <±%0,2
Thermal Runaway - <±100ppm/°C
Galvanic Isolation - Without Isolation
Memory - 100 Years, 100.000 renovation
Reaction Time - 0,2...120s
Wide range power supply
Wide range operating temperature range
DIN form B sensor head mounting
Protection against cross-connection
Galvanic isolation (1500 VDC) for model ECTC-TR-I
Economic solution with model ECTC-TR
USB configuration with USB/UART converter cable
No external power supply required for configuration
Easy-to-use Windows configuration software CoNi01
Selectable input (Pt-100, 10 type of T/C)
Temperature linear output 4 to 20 or 20 to 4 mA
Sensor Error Level can be adjusted for highest accuracy
Filter Timing constant can be adjusted
Manuals
Manual
Downloads
CoNi01 Configuration Software
Environmental Conditions
Ambient Temperature - -40...85 ºC
Protection Degree - IP00
Electrical Characteristics
Power Supply - ECTC-TR: 8...36V DC
ECTC-TR-I: 10...36V DC
Output - 4-20mA, 20-4mA
Line Resistance - Thermocouple: 10Mohm
Resolution - 16 bit
Sampling Rate - 100ms
Thermal run-away - < ±100ppm / ºC
Isolation - ECTC-TR-I: 1500V DC galvanic isolation
ECTC-TR: -
Memory - 100 years, 100.000 update
Response Time - 0.2...120s
Inputs - Pt-100 resistance thermometer -200...840 °C
Mounting : probe head-mounted
Input type : thermocouple
Applications : process
Reviews