The non-linear load, such as rectifier, convertor and switch powering supply, these electronic devices are used extensively. Harmonic, as one of the most factors to affect power quality, when being large, it can damage electrical plant directly, especially power capacity and switch, produce harmonic oscillation, burnt distribution room and damage transformer, which makes users inconvenient and power factors reduced. In order to solve this problem, besides series filter reactor with conventional capacitor to absorb a portion of harmonics, SY compensation power filter improve temperature-control function, to greatly increase its longevity.
Technical PARAMETERS
Electrical parameters – Electrical parameters –
Voltage:AC380V±10%
Compensation capacity :67~574kvar
Work frequency:50Hz/60Hz
Response time:Thyristor≤20ms,synchronous switch≤1s,AC contactor≤3s
Overload capacity:Voltage overload 1.1 times, current overload 1.3 times
Target power factor:0.8~1.0(can be set)
Control characteristics:Compensation type ,Total compensation, phase splitting compensation and hybrid compensation are optional.
Control branches :1~21 branches
Control type :Manual and automatic switching modes
Switching algorithm:Cycle switching and code switching
Protection function :Over voltage/ under voltage/ phase loss/ short circuit etc
Structural characteristics :Protection grade – IP30
Color :RAL7035(can be customized)
Installation way:Indoor installation
Environment temperature – -25℃~40℃
Humidity :up to +40℃,≤90%
Height above sea level:≤2000m(need to be customized when exceed)
Electrical characteristics : power factor, harmonic, three-phase, low-voltage
Mounting : floor-mounted, cabinet
Other characteristics : for power factor correction, with detuned filters, modular
Amperage : Min.: