Main
Range – Vigilohm
Device short name – IM10
Product or component type – Insulation monitoring device
Device application – Standard environment application Marine application
Electrical circuit type Earthing System – Medium or lowdisturbed network IT
Language – Chinese German Italian French Spanish Portuguese Russian English
Complementary Network rated voltage – 0…600 V – AC at 45…440 Hz (device connected to neutral) 0…480 V – AC at 45…440 Hz (device connected to phase) 0…345 V – DC
Type of measurement – Network insulation résistance – measurement range: 0.1 kOhm…10 MOhm
Local signalling Threshold setting – Green indicator light: satisfactory insulation résistance White indicator light: below prévention threshold Orange indicator light: below fault threshold Orange flashing indicator light: transient fault Prevent: 1 kOhm…1 MOhm Fault: 0.5…500 kOhm
Time delay range – 0…5 min for signalling circuit
Response time – <= 5 s
Auxiliary supply voltage - 110.. - .415 V AC 45...440 Hz +/- 15% 125.. - .250 V DC +/- 15%
Power consumption in VA - 12 VA
Measurement voltage - 75 V
Measurement current - 0...0.4 mA
Internai impédance - 110 kOhm - AC at 0.1...440 Hz
Options : DC
DC insulation monitorVigilohm
Schneider Electric – Electrical Distribution | France |
Categories: DC insulation monitor, Electricity - Electronics, Switch and Relay